Electromagnetic flowmeters are designed for measuring the flow of electrically conductive mediums.
The main applications can be found in the sectors district cooling, building automation and cooling water measurement.The temperature, pressure, viscosity and density have no influence on the result.

   
Features...

High accuracy

No pressure loss

Nominal sizes DN 25 - DN 1000

Flanges DIN, ANSI or JIS

Compact or remote version

As option with OIML R49 or EN 1434 type approval

   
Your benefits…
Innovative technology from a single source

Excellent Price to Quality ratio

Simple and user-friendly technology

User guidance in several languages

Robust metal housing, suitable for rugged conditions

   
 
 
Hot water meters
Type examination certificate as an electromagnetic flowmeter according to Directive 2004/22 EC category MI-001 - OIML R49. Optional: Declaration of type approval
 
Flow sensor
 
Nominal diameter DN, mm 25 32 40 50 65
  inch 1 1 1/4 1 1/2 2 2 1/2
Flange connection ANSI Art. No. 93303 93304 93305 93306 93307
Flange connection EN Art. No. 93275 93276 93277 93278 93279
Flange connection JIS Art. No. 93333 93334 93335 93336 93337

Overload flow rate

Q4, m3/h

20

31.3

50

78.8

125

Continuous flow rate Q3, m3/h 16 25 40 63 100

Transitional flow rate

Q2, m3/h 0.16 0.25 0.4 0.63 1
Minimum flow rate Q1, m3/h 0.1 0.156 0.25 0.394 0.625
 
Nominal diameter DN, mm 80 100 125 150 200
  inch 3 4 5 6 8
Flange connection ANSI Art. No. 93308 93309 93310 93311 93312
Flange connection EN Art. No. 93280 93281 93282 93283 93284
Flange connection JIS Art. No. 93338 93339 93340 93341 93342

Overload flow rate

Q4, m3/h 200 312.5 500 787.5 1250
Continuous flow rate Q3, m3/h 160 250 400 630 1000

Transitional flow rate

Q2, m3/h 1.6 2.5 4 6.3 10
Minimum flow rate Q1, m3/h 1 1.563 2.5 3.938 6.25
 
Hydraulic sensors
Type examination certificate as an electromagnetic flowmeter as part-device heat meter according to Directive 2004/22 EC, Category MI-004 - EN 1434. Optional: Declaration of type approval
 
Flow sensor
 
Nominal diameter DN, mm 25 32 40 50 65
  inch 1 1 1/4 1 1/2 2 2 1/2
Flange connection ANSI Art. No. 93317 93318 93319 93320 93321
Flange connection EN Art. No. 93289 93290 93291 93292 93293
Flange connection JIS Art. No. 93384 93385 93386 93387 93388

Maximum flow rate

qs, m3/h 7 12 20 30 50
Continuous flow rate

qp, m3/h

3.5 6 10 15 25

Minimum flow rate

qi, m3/h 0.14 0.24 0.4 0.6 1
 
Nominal diameter DN, mm 80 100 125 150 200
  inch 3 4 5 6 8
Flange connection ANSI Art. No. 93322 93323 93324 93325 93326
Flange connection EN Art. No. 93294 93295 93296 93297 93298
Flange connection JIS Art. No. 93389 93390 93391 93392 93393

Maximum flow rate

qs, m3/h 80 120 200 300 500
Continuous flow rate

qp, m3/h

40 60 100 150 250

Minimum flow rate

qi, m3/h 1.6 2.4 4 6 10
 
 
Transmitter
 
Transmitter with graphical display, 16 characters x 2 lines, local configuration via internal keys
Power supply 90 -265 VAC, 45 - 66 Hz, 5 VA Art. No. 80272
Power supply 18 - 60 VDC, 3 W Art. No. 80332
 
Transmitter without display (blind version)
Power supply 90 -265 VAC, 45 - 66 Hz, 5 VA Art. No. 80331
Power supply 18 - 60 VDC, 3 W Art. No. 80333
 
 
Option
Pressure-equalizing membrane (built-in transmitter) Art. No. 80334
 
Option on request: Programm kit (PC software incl. USB cable)
 
 
Option Remote version / Cable length:
2 m Art. No. 80335
5 m Art. No. 80336
10 m Art. No. 80337
20 m Art. No. 80338
 
 
 
 
Data management
System modules and components, Software, Software - support and maintenance
   
Downloads
Technical Documentation
 Mounting and operating instructions
Text for tenders AMFLO® MAG Pro with flange connection ANSI
Text for tenders AMFLO® MAG Pro with flange connection EN
Text for tenders AMFLO® MAG Pro with flange connection JIS
  CE - EC declaration of conformity (EN1434)
  CE - EC declaration of conformity (OIML R49)
   
Links
Order / RFQ

 

 





 

  © Aquametro
nach oben